Home » Product List » Power Transformer » 40MVA Power Transformer (SFZ-40000/33)
Product Details
40MVA Power Transformer (SFZ-40000/33)
| Packing: | Wooden Cases |
|---|---|
| Model NO.: | SFZ-40000/33 |
| Standard: | IEC Standard |
| Productivity: | 1set/4 Monthes |
| Unit Price: | Negotiable |
| Shipment Terms: | CIF |
| Payment Terms: | L/C,T/T,D/P |
| Minimum Order: | 1 Sets |
| Price Valid Time: | From Mar 27,2012 To Mar 27,2013 |
| HS Code: | 8504340000 |
| Trademark: | NINGBO VILLE |
| Origin: | Made in China |
| Phase: | Three |
| Type: | Transformer |
| Export Markets: | North America, South America, Eastern Europe, Southeast Asia, Africa, Oceania, Mid East, Eastern Asia, Western Europe |
SFZ-40000/33 Power transformer
2.1. Name: Three-phase windings OLTC dual immersion air-cooled power transformers
2-2. Type: SFZ-40000/33
2-3. Rated voltage: 33/6.9kv
2-4. Rated power: 35000/40000kVA
2-5. Rated voltage ratio: 33± 3× 2.5%/6.9kV
2-6. Rated currency: 700/3347A
2-7. PHASE: THREE PHASE
2-8. Rated Frequency: 50Hz
2-9. Connection Symbol: Dyn11
2-10. Tap changer: On load tap changer
2-11. Impedance voltage%: 13+0.8%
2-12. Cooling way: ONAN/ONAF
2-13. Winding Insulation Level
Lightning impulse withstand voltage(Kv, peak value) 1 min Frequency Pressure(kv, virtual value)
Full-wave
Latest wave
HIGH voltage SIDE: 170 185 75
Low voltage side: 75 85 35
Low-voltage neutral point: 75 35
2-14. Insulation class Class A
2-15. Transformer windings of the Inter-field strength is not more than 2 Kv / mm
2-16. Transformer loss (below 75), the no-load current and efficiency
No-load loss: 21 kW
Load loss: 198 Kw
No-load current: 0.5%
2-17. Radio frequency interference and Corona
To the greatest work of the voltage, outdoor sunny evening out line without visible Corona, radio interference voltage is not more than 2500 UV.
Inquiry Basket (