Basic Info
  • Model NO.: GCS Series
  • Rated Voltage of Assistant Circuit(V): AC 220 380(400) DC 110, 220
  • Rated Insulating Voltage (V): 660(1000)
  • Trademark: VILLE
  • Specification: ISO 9001:2000
  • HS Code: 85371090
  • Rated Voltage of Primary Circuit (V): AC 380(400, 660)
  • Rated Frequency (Hz): 50(60)
  • Protection Level: IP3l0.IP4l0
  • Transport Package: wooden case or as per requirement
  • Origin: China
Product Description
General:
GCS low voltage draw-out switchgear is suitable for power distribution system of power plants, oil and chemical industry, metallurgy industry, textile industry and high building especially in the place where requires for high automation and connection to computers such as large power plants and petrochemical industry. It adapts to 3-phase system with frequency 50 (60) Hz, rated voltage 380V (400), (660), Rated current up to 4000A, and is used for low voltage distribution equipment of power supply system, motor control center and reactive power ompensation.

Structure:
A. The main structure is made of shaped steel of type 8MF with two mounting holes (m=20mm, 100mm, and diameter=9.2mm). On both sides. It is flexible and convenient to assemble.
B. The function units are divided into three compartments: Function compartment, busbar compartment and cable compartment, each has independent function.
C. The horizontal busbars are arranged in parallel at the back of cubicle to strength their resistance to electric power, which is the basic measure to make main circuit have high intensity of short circuit.
D. The design of disconnected unit for cable makes it convenient for cable's use.

Technical Data:
Rated Voltage of Primary Circuit (V)
 
AC 380(400, 660) 
 
Rated Voltage of Assistant Circuit(V)
 
AC 220 380(400)
DC 110, 220
 
Rated Frequency (Hz)
 
50(60) 
 
Rated Insulating Voltage (V)
 
 
660(1000)
Rated Current (V)
 
Horizontal Busbar
 
≤ 4000
 
Vertical Busbar 
 
1000
 
Rated Short-time Withstand Current of Busbar ( kA/1s)
 
50,80
 
Rated Withstand Current of Busbar(peak) ( kA/0.1s) 
 
105,176
 
Power Frequency withstand Voltage( V/1min) 
 
Primary Circuit 
 
2500
 
Assistant Circuit 
 
1760
 
Busbar 
 
3 Phases 4 windingA.B.C.PEN
 
3 Phases 5 windingA.B.C.PE.N
 
Protection Level
 
IP3L0.IP4L0
 
Dimension of the body 
 
2200x(600 800 1000)x600(800 1000) 
 