Service condition
1. Altitude: ≤ 1000m (above sea level)
2. Ambient temperature: Max. 40C Min. -25C
Max. Monthly average temperature: ≤ 35C
Max. Yearly average temperature: ≤ 25C
3. Relative humidity: Daily average value≤ 95%, monthly average value≤ 90%
4. Max. Daily difference in temperature: 25C
5. Sunlight intensity: 0.1W/CM2 (wind speed 0.5M/S);
6. Outdoor wind speed: ≤ 35m/s;
7. Pollution grade: Grade III;
8. Rain proof grade: Grade 3;
9. The gradient on installation spot shall be not more than 3° ;
10. Ability of anti-earthquake: Horizontal acceleration of ground surface is 0.2g
Vertical acceleration of ground surface is 0.1g;
11. Installation spot: The spot should has no fire/explosion danger/serious pollution/chemical corrosion and exquisite shake.
Customer should negotiate with manufacturer if the service condition is different from above.
Items
Unit
Parameters
High Voltage Part
Rated voltage
kV
12
Rated frequency
Hz
50
Rated current of main busbar
A
630
1mm power frequency withstand voltage (to earth and between phases/disconnecting fracture)
kV
42/48
Lightning impulse withstand voltage (to earth and between phases/disconnecting fracture)