• Hxgn11-12 Ring Main Unit Switchgear/ Switchborad Air Insulated Switchgear
  • Hxgn11-12 Ring Main Unit Switchgear/ Switchborad Air Insulated Switchgear
  • Hxgn11-12 Ring Main Unit Switchgear/ Switchborad Air Insulated Switchgear
  • Hxgn11-12 Ring Main Unit Switchgear/ Switchborad Air Insulated Switchgear
  • Hxgn11-12 Ring Main Unit Switchgear/ Switchborad Air Insulated Switchgear
  • Hxgn11-12 Ring Main Unit Switchgear/ Switchborad Air Insulated Switchgear

Hxgn11-12 Ring Main Unit Switchgear/ Switchborad Air Insulated Switchgear

Certification: ISO9001
Shell Material: Steel Plate
Voltage Level: Medium Voltage
Installation: Fixed
Structure: Cabinet
Current: AC
Customization:
Gold Member Since 2007

Suppliers with verified business licenses

Rating: 5.0/5

Basic Info.

Model NO.
HXGN11-12 /HXGT18(HXGN26)-12(L)
Material
Cubicle Fixed Indoor AC Metal-Clad
Transport Package
Wooden Cases
Specification
IEC CE, ISO
Trademark
CNVILLE
Origin
Ningbo China
HS Code
8535300000
Production Capacity
50000 Sets/Year

Product Description

Product introduction:
Cubicle Fixed Indoor AC Metal-clad Ring Main Unit Switchgear (here in after shorted as "RMU") is a latest
version of high voltage equipment by absorbing and digesting advanced technology in domestic and abroad. It
is researched an designed an designed by our company itself for satisfying requirements of our country' s
power supply circles, specially suitable for municipal power supply net of improvement and reconstruction. After
a model approval test and a long-term running test, this product is certified to meet IEC298 standard Alternative
Current Metal-clad Switchgear and Control-gear form 1kV up to 52kV, including 52kVand meet the regulations
and specifications of reliable anti-error operation measures issued by the former State Mechanical Industry
Ministry and the former State Electricity Industry Ministry. Protection level of the product comes up to IP2X. It
features small volume, light-weight, easy operation, small operative force, safety, easy maintenance, stable and
reliable quality, free of fire disaster or explosion disaster, close to wall installation, small area occupied, etc. And
if required, a three-phases coupling function could be satisfied. Comparing and analyzing relevant foreign
documents, and through some experts evaluation, main technical data of this product comes up to the same
level as those of similar products abroad.
RMU with three phases, 10kV rated voltage, 50Hz rated frequency, is suitable for power transmission and
distribution system in places such as factory or mining enterprise, residential zone, high building, school, park,
etc. It could also be used in ring net or terminal power supply.

Brief introduction
HXGT18(HXGN26)-12(L) Box type AC metal-clad Switchgear(RMU for shorts) is designed and developed by our
company, which introduce into foreign advance technique and accord with national power supply requirement.
After the type test and long trial operation check, the product performance index has reached IEC298 AC Metal-
clad switchgear and GB3906 3-35KV AC Metal-clad switchgear, and meet the reliable fault prevention operation
function of the two parts requirements, protection degree reached IP2X. This product features small bulk, light
weight, easy operation, safety operation, easy maintenance, etc. It is a newly type of high voltage switchgear
suitable formunicipal power net improvement and reconstruction.Switchgear Basic Technical Parameters

Service condition
a. Altitude≤1000m
b. Ambient air temperature: Maximum +40ºC Minimum -35ºC
c. Relative humidity: Diary average value shall be not more than 95%; monthly average value shall be not more
than 90%.
d. Ambient air should be with no corrosion, no apparent pollution with combustible gas and etc.
e. Earthquake prevent function: process ground horizontal acceleration0.2g and vertical acceleration0.1g at the
same time, adopt resonance,sine,whip wave test, safety factor should be more than 1.67
Hxgn11-12 Ring Main Unit Switchgear/ Switchborad Air Insulated Switchgear
Technical parameter
Technical data of RMU
S/N Description Unit Data
1 Rated voltage kV 12
2 Rated frequency Hz 50
3 Rated current of main busbar A 630
4 Rated short-time withstand current of main circuit, earth circuit kA/s 25/2
5 Rated peak withstand current of main circuit, earth circuit kA/s 63
6 Rated short circuit making current of main circuit, earth circuit kA/s 63
7 LBS full capacity breaking times times 100
8 Fuse breaking current kA/s 31.5 40
9 Mechanical endurance times 10000
10
 
1 min power frequency withstand voltage
phase to earth kV 42
phase to phase/ between isolating clearance kV 48
11
 
Lightning impulse withstand voltage (peak)
phase to earth kV 75
phase to phase/ between isolating clearance kV 85
12 1 min power frequency withstand voltage of Secondary circuit kV 2

Performance data of SF6 LBS and SF6 LBS+fuse
S/N Description Unit LBS LBS+fuse
1 Rated voltage kV 12
2 Rated frequency Hz 630 125
3 Rated current of main busbar  A 50
4
 
1 min power frequency withstand voltage
phase to earth kV 42
phase to phase/ between isolating clearance kV 48
5
 
Lightning impulse withstand voltage (peak)
phase to earth kV 75
phase to phase/ between isolating clearance kV 85
6 Rated short time withstand voltage kA/s 25/2 --
7 Rated peak withstand voltage kA/s 63 --
8 Rated short circuit making current kA/s 63 80 (peak)
9 Capacitor bank breaking current A 400
10 Rated no load transformer breaking current A no load current of 1600kVA transformer
11 Main circuit resitance <85
12 Rated short circuit breaking current kA -- 31.5
13 Rated transfer current A -- 1500
14 Mechanical endurance times 10000
15 Rated SF6 gas pressure ( 20ºC surface pressure) Mpa 0.04
16 Motor operation power voltage V AC 48, AC/DC 220 110
17 Closing motor current A 0.5
18 Opening current  A 0.5
Hxgn11-12 Ring Main Unit Switchgear/ Switchborad Air Insulated Switchgear
Our Services
1. Pre sale service
a. make technical solution
b. send quotation, technical data sheet and drawing
c. prepare power transmission plan, testing plan and shipment plan
2. In sale service
a. supervise the manufacturing schedule totally in accordance with the plan
b. send photos to customer during every manufacturing process(hold point)
c. inform the customer one week before testing.
3. After sale service
a. installation and commissioning, training the workers
b. quick response within 12 hours any time
c. provide 12 months guarantee period normally.

FAQ
1. Q: What is your delivery time ?
A:  Depend on the type of transformer.
2. Q: What is your payment term?
A:  30% advance by T/T , 70% before delivery by T/T or L/C or we can discuss about it.
3. Q: What kind of standard you follow?
A:  IEC, ANSI, CSA, GB, etc
4. Q: What kind of supporting documentation you can provide normally
A:  Quotation, outline drawing, manufacturing plan, quality control plan
testing plan, financial report, type test report(KEMA, CESI),reference list, etc
5. Q: What is your normal warranty period?
A:  12 months after transformer operation.
6. Q: Can u do installation and commission in user's site?
A:  Yes, we can send our installation team to user's country for service.
7. Q: Do you have any experience in this kind of transformer?
A:  Yes, we can provide reference list for check.
 
Our advantages:

Quality Assurance
--From the very beginning, VILLE ensures quality in every step to achieve the best quality.
 Experience Sharing
--With more than 30 years' experience in power industry, VILLE brings you an optimized solution.
 Global Service
--Wherever you are, VILLE global network will support and provide you with value.
 Quick Response
--In response to your needs without delay, VILLE  knows the value of your time.
 
Thanks for choosing VILLE as your reliable partner and please trust both
of us will create a brilliant future!

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

Gold Member Since 2007

Suppliers with verified business licenses

Rating: 5.0/5
Management System Certification
ISO 9001, ISO 9000, ISO 14001, ISO 14000, ISO 20000, IATF16949, ISO 14064, QC 080000, ANSI/ESD, ISO 29001, ISO 50001
Import & Export Mode
Have Own Export License
Terms of Payment
LC, T/T, D/P, PayPal, Western Union, Small-amount payment, Money Gram