Item | Unit | Data | |||
HV Unit | Switch type | Combined electrical apparatus |
Circuit breaker | ||
Rated voltage | kV | 40.5 | 40.5 | ||
Rated frequency | Hz | 50 | 50 | ||
Rated current | A | 630 | 1250 | ||
1 min Rated power frequency withstand voltage(for ground and phase / isolation fracture) |
kV | 95/118 | 95/118 | ||
Lighting withstand voltage(for ground and phase / isolation fracture) |
kV | 185/215 | 185/215 | ||
Rated short time withstand current | kA/s | 20/2 | 25/4 | ||
Rated peak withstand current | kA | 50 | 63 | ||
Rated short-circuit current | kA | 31.5 | 63 | ||
Rated short circuit breaking current | kA | 31.5 | 25 | ||
LV Unit | Rated voltage | V | 690/270 | ||
Main circuit rated current | A | 1600~3300 | |||
Rated ultimate short circuit breaking capacity | kA | 50 | |||
Rated short-circuit breaking capacity | kA | 40 | |||
Rated short-time withstand voltage | kA/s | 40/1 | |||
Transformer Unit |
Rated capacity | kVA | 1000~5500 | ||
Impedance voltage | % | 6.5 | |||
Tapping range | % | ±2 x 2.5 ; ± 5 | |||
Connected group | D, yn11 or Y , d11 d 11 | ||||
Main body |
Enclosure degree of protection | HV room | IP33 | ||
LV room | IP33 | ||||
Transformer room | IP23 | ||||
Sound level | dB | ≤55 |