• Drawable Type AC Metal-Clad Switchgear (KYN1-12)
  • Drawable Type AC Metal-Clad Switchgear (KYN1-12)
  • Drawable Type AC Metal-Clad Switchgear (KYN1-12)
  • Drawable Type AC Metal-Clad Switchgear (KYN1-12)
  • Drawable Type AC Metal-Clad Switchgear (KYN1-12)
  • Drawable Type AC Metal-Clad Switchgear (KYN1-12)

Drawable Type AC Metal-Clad Switchgear (KYN1-12)

Certification: ISO9001:2000
Shell Material: Stainless Steel
Voltage Level: High Voltage
Installation: Fixed
Structure: Protection
Current: AC
Customization:

Contact Supplier

Mr. Green Hsu
Commerical Manager
Gold Member Since 2007

Suppliers with verified business licenses

Rating: 5.0/5

Basic Info.

Model NO.
KYN1-12
Type
Distribution Metering Box
Form
All- Packaged Type
Operation Voltage
High Voltage
Size
1 Uint
Application Range
Power Plants
Shell Protection Grade
IP55
Brand
Ville
Rated Voltage
10kv
Enclosure Material
2.5mm Cold Rolled Steel Sheet
Rated Current
630, 1250, , 3150
Rated Short-Circuit Breaking Current
20, 31.5, 40
Rated Short-Circuit Making Current
50, 80, 100
Mechanical Endurance
>10000
Rated Current Breaking Times
>10000
Degree of Protection
IP2X
Transport Package
Wooden Packing
Specification
iEC CE, ISO
Trademark
VILLE
Origin
Ningbo China
HS Code
85
Production Capacity
50000 Sets/Year

Product Description

General:
KYN1-12 drawable type AC metal clad switchgear is used in 10kV, three phases, 50Hz power supply system for 
controlling, transmission and distribution. With several year's experiences on improving design, this kind of 
switchgear is suitable to be used in frequent operations specially and a new type of reinforced insulation and 
busbar with bypass has been developed update.
The design and structure of the switchgear conforms to IEC standards and GB 3906-91 standards. It has
welding and package structure. The protection level of its enclosure is IP2X. It consists of trolley, front cubicle,
back cubicle, instrument room of relay and the small busbar room on its ceiling. The front switchgear and the
back switchgear are connected by bolts, the instrument room of relay and the body are connected by vibration
absorber; Other parts are separated by steel sheets. It has the function of aerial incoming and outgoing line,
cable incoming and outgoing and liaison between left parts and right parts.

Structure:
The enclosure of KYN1-12 indoor AC metal-clad draw-out switchgear is welded by bent steel plates. It consists 
of four parts: instrument compartment, front compartment, rear compartment and truck compartment. A kind of 
bolt connection is used in between the front compartment and the rear compartment. And a kind of shock 
absorber is used in between the instrument compartment and the enclosure. Steel plates separate each 
compartment. Several schemes could be available, such as overhead incoming and outgoing, cable incoming 
and out-going, contact to left or contact to right, etc.
 
Product feature:
KYN1-12 truck type 10KV HV Switchgear is complied with International Standards as well as Nation Standards.
It is a draw out truck trolley cubicle. Both of the enclosure and isolating plate of each functional units is made of
2.5mm cold rolled steel sheet, the surface is treated with phosphatization, anticorrosion, static plastic-pouring;
Each part is connected by bolt of high intensity. It is featured by beautiful looking, easy installation and
maintenance.

The frame of the trolley is made of cold rolled steel sheets in the process of punching and welding. The trolley
has separate exhaust passage to the ceiling. Varieties of trolley have the same height and depth, so truck with
the same specification can be interchanged. There are isolating position, testing position and working position
inside the trolley, each of them has orientation device and position indicator. The trolley can be seen on each
position as well as seen on the position indicator. When the trolley goes into the switchgear, the enclosure can
be connected with earthing system of the switchgear. There are controlling indicator and off and on indicator of
the spring mechanism of the circuit breaker on the panel of the truck.

The guide rails of the circuit breaker room are firm and flat. The truck can run smoothly on the working position
and testing position. The valve is made up of nonmetallic insulating epoxy plates. When the truck is on the
isolating position/ testing position, the static contact and the moving contact of the major loop are isolated by
valve; When the truck enters into the working position, the valve opens automatically. The off and on condition
of the circuit breaker, off and on mechanical position indicators and stored energy/ released energy indicator
can be seen on the panel of the trolley. Only when the isolating plates between the truck room and cable
compartment are pulled out, can the worker get into the switchgear to install or maintain the cable.

On the upper part of the trolley room, busbar room and cable room, there is compression release device. When
the internal fault arc occurs in the circuit breaker or busbar room and cable room, the compression release
metal plates at the ceiling opens automatically.

Ordering notice:
Please provide the followings
A. Main wiring scheme code, single line system diagram, pareto diagram and layout plan.
B. Secondary principle diagram, terminal pareto diagram. If without it, conform with the manufacturer's terminal
pareto diagram.
C. The type, specification and quantity of the electrical components of switchgear.
D. Summary table of electrical equipment.
E. Please provide span and height dimensions if busbar bridge(between two ranks of switchgear or between
switchgear and wall) is needed.
F. Please indicate if switchgear shall be on the special condition.
G. Please indicate type and quantity of other accessories, if necessary.  

Main Technical Data:
Rated Voltage (kV) 12
Rated Current (A) 630, 1250, , 3150
Rated short-circuit breaking current (KA) 20 ,31.5, 40
Rated short-circuit making current (KA) 50, 80, 100
Rated peak withstand current (peak value) (kA) 50, 80, 100
Rated short-time withstand current (r.m.s.) (kA/s) 20/4, 31.5/4, 40/4
Rated 1min power frequency condenstaion 
withstand voltage (kV)
42
Isolating distance insulation withstand voltage power
 frequency/lighting impulse (kV)
48/85 (peak value)
Phase to phase and phase to earth insulation 
withstand volatge power frequency/lighting impulse (kV)
42/75 (peak value)
Nominal creepage distance (mm/kV) 20
Mechanical endurance >10000
Rated current breaking times >10000
Rated short-current breaking times 50, 30
Opening time (S) <0.06
Closing time (S) <0.1
Degree of protection IP2X
Operation mechanism and operation voltage (AC or DC) DC 110,220 AC220
Weight (including packing ) kg <800
Dimensions (Width×Depth×Height) mm 800×1500×2200  840×1500×2200  
880×1500×2200  
1000×1650×2200
Packing dimensions (Width×Depth×Height)   mm 1000×1750×2500  1040×1750×2500  
1080×1900×2500  
1200×1900×2500
Drawable Type AC Metal-Clad Switchgear (KYN1-12)
Our Services
1. Pre sale service
a. make technical solution
b. send quotation, technical data sheet and drawing
c. prepare power transmission plan, testing plan,and shipment plan
2. In sale service
a. supervise the manufacturing schedule totally in accordance with the plan
b. send photos to customer during every manufacturing process(hold point)
c. inform the customer one week before testinng.
3. After sale service
a. installation and commissioning, training the workers
b. quick response within 12 hours any time
c. provide 12 months gurantee period normally.

FAQ
1. Q: What is your delivery time ?
A:  Depend on the type of transformer.
2. Q: What is your payment term?
A:  30% advance by T/T , 70% before delivery by T/T or L/C or we can discuss about it.
3. Q: What kind of starndard you follow?
A:  IEC, ANSI, CSA, GB, etc
4. Q: What kind of supporting documentation you can provide normally
A:  Quotation,outline drawing,manufacturing plan, quality control plan
testing plan, financial report, type test report(KEMA, CESI),reference list,etc
5. Q: What is your normal wanrranty period?
A:  12 months after transformer operation.
6. Q: Can u do installation and commissioningin user's site?
A:  Yes, we can send our installation team to user's country for service.
7. Q: Do you have any experience in this kind of transformer?
A:  Yes, we can provide reference list for check.
8. Q: Are you manufacturer or trading company?
A:  Manufacturer with own import & export company.
  
Our advantages:
Quality Assurance
--From the very beginning, VILLE ensures quality in every step to achieve the best quality.
 Experience Sharing
--With more than 30 years' experience in power industry, VILLE brings you an optimized solution.
 Global Service
--Wherever you are, VILLE global network will support and provide you with value.
 Quick Response
--In response to your needs without delay, VILLE  knows the value of your time.
 
Thanks for choosing VILLE as your reliable partner and
please trust both of us will create a brilliant future!

Send your message to this supplier

*From:
*To:
avatar Mr. Green Hsu
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

Contact Supplier

Mr. Green Hsu
Commerical Manager
Gold Member Since 2007

Suppliers with verified business licenses

Rating: 5.0/5
Management System Certification
ISO 9001, ISO 9000, ISO 14001, ISO 14000, ISO 20000, IATF16949, ISO 14064, QC 080000, ...
Import & Export Mode
Have Own Export License
Terms of Payment
LC, T/T, D/P, PayPal, Western Union, Small-amount payment, Money Gram