Introduction
This type of tap changer has two kinds of products, they are of vertical type and horizontal type. It is usually
used in three-phase and single-phase oil-immersed power transformer with frequency of 50, 60 Hz, rated
voltage 10~66 kV, rated current from 63A to 1000A. It can be regulated on middle or neutral terminal. It can be
equipped directly on transformer tank or transformer tank wall working under non-energized condition.
Off-circuit Capacity Regulating Tap Changer
This type of tap changer is designed as step changeable facility used for capacity regulating transformer under
non-energized condition. It is suitable for three-phase oi-immersed capacity regulating with voltage rated 10kV
and below, rated capacity 315kVA and below. It can be connected in series and parallel system on LV and HV
windings or connected b star or delta method through which to realize transformer capacity changeable. By this
way we can reduce iron loss and increase transformer load efficiency and power factor avoiding the
phenomenon of "Big horse will drag small carriage", and can be used to regulate voltage terminals
Type of tap changer |
Install Dimenson (mm) |
Holes on tank
cover (mm) |
H |
H1 |
H2 |
H3 |
L |
Y |
Md |
WSL II 125/10-4×3L |
323 |
25 |
106 |
65 |
52 |
196 |
M8 |
φ43 |
WSL II 250/10-4×3L |
323 |
25 |
106 |
65 |
52 |
212 |
M10 |
φ43 |
WSL II 400/10-4×3L |
474 |
28 |
141 |
105 |
45 |
258 |
M16 |
φ43 |
WSL II 630/10-4×3L |
474 |
28 |
141 |
105 |
45 |
270 |
M18 |
φ43 |
WSL II 125/10-6×5L |
323 |
25 |
106 |
65 |
52 |
196 |
M8 |
φ43 |
WSL II 250/10-6×5L |
323 |
25 |
106 |
65 |
52 |
212 |
M10 |
φ43 |
WSL II 400/10-6×5L |
474 |
28 |
141 |
105 |
65 |
298 |
M16 |
φ43 |
WSL II 630/10-6×5L |
474 |
28 |
141 |
105 |
65 |
310 |
M18 |
φ43 |
WSL II 125/10-8×7L |
323 |
25 |
106 |
65 |
65 |
240 |
M8 |
φ43 |
WSL II 250/10-8×7L |
323 |
25 |
106 |
65 |
65 |
256 |
M10 |
φ43 |
WSL II 125/35-4×3L |
598 |
25 |
178 |
130 |
55 |
204 |
M8 |
φ43 |
WSL II 250/35-4×3L |
598 |
25 |
178 |
130 |
55 |
220 |
M10 |
φ43 |
WSL II 400/35-4×3L |
625 |
28 |
184 |
138 |
45 |
258 |
M16 |
φ43 |
WSL II 630/35-4×3L |
625 |
28 |
184 |
138 |
45 |
270 |
M18 |
φ43 |
WSL II 125/35-6×5L |
598 |
25 |
178 |
130 |
55 |
244 |
M8 |
φ43 |
WSL II 250/35-6×5L |
598 |
25 |
178 |
130 |
55 |
260 |
M10 |
φ43 |
WSL II 400/35-6×5L |
625 |
28 |
184 |
138 |
65 |
298 |
M16 |
φ43 |
WSL II 630/35-6×5L |
625 |
28 |
184 |
138 |
65 |
310 |
M18 |
φ43 |
WSL II 125/66-4×3L |
1082 |
25 |
300 |
250 |
50 |
232 |
M8 |
φ43 |
WSL II 250/66-4×3L |
1082 |
25 |
300 |
250 |
50 |
248 |
M10 |
φ43 |
WSL II 125/66-6×5L |
1082 |
25 |
300 |
250 |
55 |
332 |
M8 |
φ43 |
WSL II 250/66-6×5L |
1082 |
25 |
300 |
250 |
55 |
348 |
M10 |
φ43 |
WSL IV 125/35-3×2L(Y-Delta) |
598 |
25 |
178 |
130 |
55 |
308 |
M8 |
φ43 |
WSL IV 250/35-3×2L(Y-Delta) |
598 |
25 |
178 |
130 |
55 |
324 |
M10 |
φ43 |
company profile:
Main product line: Tap changer and HV switchgear
Tap changer manufacturing with fullest vertical integration
Tap Changer Products Range On-Load Tap Changer:
* Conventional OLTC for transformer with voltage up to 765kV
*Vacuum OLTC for oil transformer with voltage up to 765kV
*Vacuum OLTC for dry transformer with voltage of 72.5kV
Off-Circuit Tap Changer
* Application for the transformer with voltage up to 765kV
Our advantages:
Quality Assurance
--From the very beginning, VILLE ensures quality in every step to achieve the best quality.
Experience Sharing
--With more than 30 years' experience in power industry, VILLE brings you an optimized solution.
Global Service
--Wherever you are, VILLE global network will support and provide you with value.
Quick Response
--In response to your needs without delay, VILLE knows the value of your time.
Thanks for choosing VILLE as your reliable partner and
please trust both of us will create a brilliant future!