1.1.1 GENERAL TECHNICAL DATA | ||
Highest voltage | 36kV | 50Hz |
Operating voltage | 33 kV±5% | 50Hz |
Voltage for aux. drivers | 380V | 50Hz |
Control voltage | 220V | 50Hz |
Interlock voltage | 220V | 50Hz |
PLC signals | 24V | DC |
Ambient temperature max./min. | 45 / - 10 | Deg. C |
Altitude | 1500 | m |
Humidity | 80 | % |
1.1.2 TRANSFORMER DATA | ||
Operating voltage | 33kV±5% | |
Frequency | 50Hz ±1% | |
Operation | Continuously | |
EAF transformer rated capacity | MVA (+ 20% Overload) | |
Rated current | 2449.4 A (+ 20% Overload) | |
Reactor Rated Power | 18 MAVR (25.92 MVA Overload) | |
Reactance in normal tap | 1 Ω | |
Number and ratio of taps | 6 taps: 100%-80%-60%-40%-20%-0 |
|
Insulation level Winding: Um: AC: BIL: |
Full insulation HV 52 kV 95 kV 250 kV |
|
Protection level | IP54 | |
Vector group | III | |
System short circuit capacity | 1500 MVA | |
Short circuit duration | 6 sec | |
Short circuit times | 2.5 times | |
Regulation method | Off circuit | |
Type of tap changer | NLTC Off -circuit motor drive | |
Manufacturer | Shanghai Huaming / China (ZUNYI) | |
Model | 2*ZWL III-1600/40- 6 taps | |
Number of taps | 6 | |
Reactor Winding Materials | Copper | |
Cooling Type | OFWF |
Suppliers with verified business licenses