New graphite material project ZHS-2×60kA / 200V 12 phase rectifier DC Rectiformers in single and parallel New graphite material project 12 phase rectifier cabinet
Product Description
1, Adaptive conditions and performance indexes of rectifier
1. Application scope and basis
The application scope of this technical scheme is limited to 30000t/year new graphitized material engineering rectifier.Including technical specifications for functional design, structure, performance, installation and test of rectifier unit body and supporting equipment meeting the requirements of the project.
The standards and technical requirements on which the technical scheme is based are based on national GB and international IEC standards and the latest in the industry
New standard JB and user technical specification for DC rectifier (1).
2. Basic design electrical conditions
2.1 rated condition of single unit rectifier:
DC voltage: udn = 40-200v
DC current: IDN = 2×60KA
2.2 overall configuration:
The single unit 120kva consists of one on load voltage regulating rectifier transformer with two diode rectifiers.Each diode rectifier outputs DC current of 60kA and DC
voltage of 40-200v. Each diode rectifier is 6-phase rectifier. The two rectifiers are connected in parallel to form equivalent 12 pulse wave and output DC current of 2×60kA,
DC voltage 40-200v Or a single unit 120ka consists of an on load voltage regulating rectifier transformer with a diode rectifier, with an output DC current of 120ka and a
DC voltage of 40-200v.
Single unit 12 pulse, two units in parallel to form a 24 pulse rectifier system.
2.3 the rectifier line adopts double inverse star with balance reactor, which is fixed inside.
2.4 electrical conditions for normal use
2.4.1 power supply voltage: 20kV ± 5%
2.4.2 frequency: 50Hz ± 0.5
2.4.3 number of phases: 3
2.4.4 power supply: AC380 / 220V ± 5%
2.4.5 control protection: AC220V ± 5% or dc220v
Frequency: 50Hz ± 0.4
3. Cooling of rectifier:
3.1 cooling method: use deionized high-purity water for cooling.
3.2 layout of cooling water circuit: the main manifold of component cooling water circuit is located at the bottom of rectifier cabinet and adopts pure water cooling mode.
3.3 cooling water circuit materials: the cooling water pipe, nozzle and flange of rectifier cabinet are made of stainless steel or PVC materials, and the water pipe Selection
of high quality anti-aging, corrosion resistant hose.The pressure and temperature measuring points are installed in the middle of the manifold and in the pure Thermal
resistance for centralized monitoring (installed in rectifier cabinet) shall be set at the water outlet pipe.
3.4 pressure of cooling circulating water: the water pressure shall not be less than 0.10MPa and 0.15Mpa in normal operation.
4. Installation method:
The rectifier device is fixed indoors, located on both sides of the rectifier transformer and directly grounded.
5. Application: graphitized products.
6. Natural conditions:
Rectifier room absolute air temperatureat maximum site ambient °C 50
Pollution level: Grade III
| Ser.No. |
Description |
Unit |
Design |
Seller |
| |
| Item 1 |
Auto-Regulation / Rectifier Transformer Combination |
|
| 1 |
Supply voltage |
V |
20,000 |
20,000 |
| 2 |
Frequency |
Hz |
50 |
50 |
| 3 |
Maximum short-circuit power |
MVA |
866 |
866 |
| |
Auto-Regulation Transformer: |
|
| 4 |
Number of transformers |
pc. |
2 |
2 |
| 5 |
Throughput rating per unit |
MVA |
|
28 (+20%) |
| 6 |
Vector group |
- - |
|
D(+7.5°)/y11 ; D(-7.5°)/y11 |
| 7 |
Short circuit impedance |
% |
|
4- 6 |
8 |
Tap charger operation |
- - |
motor operation |
motor operation |
| 9 |
On-load tap charger positions |
- - |
70 positions |
71 Pos.(MR Tap-changer) |
| 10 |
OLTC tap step |
V DC |
2.3 |
2.33(with saturable reactor ) |
| 11 |
Off circuit tapping switch |
- - |
3 positions |
N.A |
| |
Rectifier Transformer: |
(with IPT and Saturated Reactor) |
| 12 |
Primary voltage |
V |
adapted to output of step-down transformer |
adapted to output of step-down
transformer |
| 13 |
Primary rating per unit at max secondary voltage |
MVA |
|
28 |
| 14 |
Secondary rating per unit at max secondary voltage |
MVA |
|
396 |
| 15 |
Maximum secondary voltage, at no load |
V |
|
330 V (A.C) 200 V(DC) |
| 16 |
Minimum secondary voltage, at no load |
V |
|
69.8 V (AC) 40 V(DC) |
| 17 |
Short circuit impedance |
% |
|
6-7 |
2. Rectifier transformer for export to chemical industry
6.110kV class direct-down on-load voltage regulation phase-shifting rectifier transformer
7. 110KV on-load regulating rectifier transformer in chemical industry
8. Strong oil-water cooling rectifier transformer
Company Profile
PRODUCTION FACILITY
REFERENCE PROJECT:
Company Introduction
NingboVille Enterprise Co.,Ltd. is a combination of Transformer R&D center, production, sales and after sales service,possesses of strong technical strength and excellent manufacturing equipments, as well as modern Office facilities.
It specially produces large scale power transformer and industrial transformers of high quality and reliability. A large share of its resources are devoted to research and
development of industrial and special transformers and reactors for any special application,such as the iron and steel and electrometallurgical industries.The company main working is suppling,engineering,designing,manufacturing, executing, and commissioning for transformer .
Why Choose Us
FIRST-CLASS PROCESSING AND TEST EQUIPMENT
We have more than 500 sets of sophisticated, advance production and test equipments, complete and perfect processing equipments, and scientific and rational processing technology, which guarantee first-class products, Authorized by the Bureau of Zhejiang Technology Supervision, Quzhou,Fangyuan Inspection Company of Power Transmission and Transformation Equipment, whick is based on our testing center, undertakes the quality inspection of the industry in our province, this is a solid guarantee for our excellent product quality.
BEAUTIFUL ENVIRONMENT
We are confident that good products come from good personnel, and good environment makes qualified personnel. The company is committed to creating a garden-like working environment for employees. We have green belts, modern standardized workshops and well-planned parks where we sow our youth; we work hard, so we are harvesting the future.
With the first-class quality products, reasonable price and excellent after-sale services.product not only best-selling all over the country,but also in the international market have higher credit, such as Thailand, Vietnam, Myanmar, Indonesia,alaysia,Philippines, Ethiopia and Nigeria,Saxonstan,Uzbekistan, Korea, Turkey, Sudan, Iran etc. especially in the steel enterprises, VILLE production of transformers already have high reputation.
Our Performance:
| 1. |
Pre sale service |
| a. |
make technical solution |
| b. |
send quotation, technical data sheet and drawing |
| c. |
prepare power transmission plan, testing plan,and shipment plan |
| 2. |
In sale service |
| a. |
supervise the manufacturing schedule totally in accordance with the plan |
| b. |
send photos to customer during every manufacturing process(hold point) |
| c. |
inform the customer one week before testinng. |
| 3. |
After sale service |
| a. |
installation and commissioning, training the workers |
| b. |
quick response within 12 hours any time |
| c. |
provide 12 months gurantee period normally. |
FAQ For You
| 1. Q: |
What is your delivery time ? |
| A: |
Depend on the type of transformer. |
| 2. Q: |
What is your payment term? |
| A: |
30% advance by T/T , 70% before delivery by T/T or L/C or we can discuss about it. |
| 3. Q: |
What kind of starndard you follow? |
| A: |
IEC, ANSI, CS*A, GB, etc |
| 4. Q: |
What kind of supporting documentation you can provide normally |
| A: |
Quotation,outline drawing,manufacturing plan, quality control plan,testing plan, financial report, type test report(KEMA, CESI),reference list,etc |
| 5. Q: |
What is your normal wanrranty period? |
| A: |
12 months after transformer operation. |
| 6. Q: |
Can u do installation and commissioningin user's site? |
| A: |
Yes, we can send our installation team to user's country for service. |
| 7. Q: |
Do you have any experience in this kind of transformer? |
| A: |
Yes, we can provide reference list for check. |
| 8. Q: |
Are you manufacturer or trading company? |
| A: |
Manufacturer and Trading company. |
Our advantages:
Quality Assurance
--From the very beginning, VILLE ensures quality in every step to achieve the best quality.
Experience Sharing
--With more than 30 years' experience in power industry, VILLE brings you an optimized solution.
Global Service
--Wherever you are, VILLE global network will support and provide you with value.
Quick Response
--In response to your needs without delay, VILLE knows the value of your time.
Thanks for choosing VILLE as your reliable partner and please trust both of us will create a brilliant future!