Technical parameters:
-
|
Manufacturer |
|
|
NINGBO VILLE |
-
|
Manufacturer's name |
|
|
Ningbo Ville Enterprise Co., Ltd |
-
|
Country of origin |
|
|
China |
-
|
Applicable standard |
|
Comply with standards as specified in item 1.0 |
IEC60076 |
-
|
Standards of quality management |
|
ISO 9001 |
ISO 9001 |
-
|
Service conditions |
|
|
Outdoor |
-
|
Ambient temperature |
|
|
|
|
- Maximum |
0C |
40 |
40 |
|
- Minimum |
0C |
-10 |
-10 |
|
- Maximum yearly average |
0C |
25 |
25 |
-
|
Maximum relative humidity |
% |
83 |
83 |
-
|
Altitude above sea level |
m |
445 |
445 |
-
|
Climate |
|
|
|
|
Key specifications |
|
|
|
-
|
Type |
|
Outdoor installation, Three-phases, oil-immersed, two windings |
Outdoor installation, Three-phases, oil-immersed, two windings SZ-15000/33 |
Puissance nominale: 15MVA Tension primaire: 33KV Tension secondaire: 15KV Groupe de vecteurs: Dyn11 Refroidissement: ONAN Fréquence: 50 Hz Phase: trois Enroulement: cuivre Taraudage: -15% à + 5%, 1,25% à chaque pas, total 17 positions de prise. Aucune perte de charge: 11kw Sur la perte de charge: 75kw Impédance: 10% Accessoires: Indicateur de température d'enroulement, indicateur de température d'huile, indicateur de niveau d'huile, etc. Poids approximatif: Réservoir et accessoires: 1800 kg Partie active: 15000kg Huile: 9700kg Transport: 28400kg Total: 36500kg Condition d'utilisation : 40°C maximum annuelle de température à
When you choose our company product, please offer following data:
2nd.Transformer Type:
3rd .Rated voltage:
4th .Rated capacity:
5th .Rated voltage ratio:
6th .Rated current:
7th. Phase number:
8th .Rated frequency:
9th. Connection set:
10th. Voltage regulating method:
11th. Short circuit impedance:
12th. Cooling mode:
13th Transformer loss (under 75ºC),no-load current and efficiency
No-load Loss: kW According to IEC standard
Load Loss: kW According to IEC standard
No-load current: % According to IEC standard