Customization: | Available |
---|---|
Application: | Power |
Phase: | Three |
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
|
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Rated Capacity(KVA): | 63 |
Rated Voltage HV(KV): | 69 |
Rated Voltage LV(KV): | 6.3 |
HV Tapping Range: | ± 8 x 1.25% |
Vector group: | YNd11 |
No-load Losses(KW): | 56.2 |
Load Losses(KW): | 0.35 |
No-load Current(%): | 222.3 |
Impedance Voltage(%): | 9 |
Reference Temperature | ° C | 75 | ||||
No-Load Losses at Principal Tapping: | W | 9.0 kW | ||||
Looses of Cooling Fan System | W | / | ||||
Insulation Levels (LI/AC): | LI325AC140/LI125AC55 | |||||
No Load Current: | @ Un | % In | 0.56 | |||
@ 1.05 Un | % In | 0.68 | ||||
Sound Level: | dB | < 67 | ||||
Short Circuit Impedance at Principal Tapping: | P/S | % Un | 8~10% | |||
P/T | % Un | |||||
S/T | % Un | |||||
Reference Temperature | ° C | 75 | ||||
Top Oil Temperature Rise: | °C | 51K | ||||
Average Winding Temperature Rise: | °C | 64K | ||||
Insulation Resistance (Reference Temperature = 20°C): | ||||||
HV/LV / | Mohms | ≥1000 | ||||
HV/GR - LV/GR - | Mohms | ≥1000 |
Reference project:
Our advantages:
Quality Assurance
--From the very beginning, VILLE ensures quality in every step to achieve the best quality.
Experience Sharing
--With more than 30 years' experience in power industry, VILLE brings you an optimized solution.
Global Service
--Wherever you are, VILLE global network will support and provide you with value.
Quick Response
--In response to your needs without delay, VILLE knows the value of your time.