1200kVA Oil Type Motor Starting Auto Transformer 4.16kv

Product Details
Customization: Available
Application: Power
Phase: Three
Still deciding? Get samples of US$ 500/Piece
Request Sample
Gold Member Since 2007

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Management System Certification
ISO 9001, ISO 9000, ISO 14001, ISO 14000, ISO 20000, IATF16949, ISO 14064, QC 080000, ANSI/ESD, ISO 29001, ISO 50001
Import & Export Mode
Have Own Export License
Terms of Payment
LC, T/T, D/P, PayPal, Western Union, Small-amount payment, Money Gram
  • 1200kVA Oil Type Motor Starting Auto Transformer 4.16kv
  • 1200kVA Oil Type Motor Starting Auto Transformer 4.16kv
  • 1200kVA Oil Type Motor Starting Auto Transformer 4.16kv
  • 1200kVA Oil Type Motor Starting Auto Transformer 4.16kv
  • 1200kVA Oil Type Motor Starting Auto Transformer 4.16kv
  • 1200kVA Oil Type Motor Starting Auto Transformer 4.16kv
Find Similar Products

Basic Info.

Model NO.
Auto Transformer
Core
Core-type Transformer
Cooling Method
Oil-immersed Type Transformer
Winding Type
Auto-transformer
Certification
ISO9001-2000
Usage
Power Transformer, Distribution Transformer
Frequency Characteristics
Power Frequency
Shape of Core
Ring
Brand
Ville
Transport Package
Wooden Case
Specification
Customized
Trademark
VILLE
Origin
Ningbo
HS Code
85
Production Capacity
500 Sets Per Month

Product Description

Three phase self coupling step-down starting transformer - Product overview: The  three-phase self coupling step-down starting transformer is
suitable for AC 50Hz, rated voltage 380V, and rated output capacity 14KW-3000KW.
Technical:Starting Autotransformer
1200KVA - 4.16kV - oil insulated
o Rated power: 1200KVA
o Rated engine power: 1200KVA
o Starters per hour: 5 (five)
o Engine start time: 14 seconds
o Minimum interval between starts: 10
minutes
o Consecutive starters: 2 (two)
o Primary rated voltage: 4160V
o Number of phases: 3 (three)
o Secondary rated voltage:
3328/2704/2080V - (80% / 65% / 50%)
o Frequency: 60Hz
o Insulating material: mineral oil
o Pt-100 oil/copper sensors for remote
monitoring/indication of temperature.
It is often used for infrequent step-down starting of large capacity squirrel cage asynchronous motors to improve the impact on the transmission
network during motor starting. Although it is an old-fashioned starting device, the use of its multiple tap depressurization can not only adapt to the
needs of various load starting, but also obtain larger starting torque. Its function is to use the characteristics of transformer depressurization to
reduce the starting current of the motor. Three phase self coupling step-down starting transformer - Applicable occasions: Suitable for infrequent
step-down starting of three-phase squirrel cage asynchronous motors with a power of 14KW-3000KW.
1200kVA Oil Type Motor Starting Auto Transformer 4.16kv

1200kVA Oil Type Motor Starting Auto Transformer 4.16kv
1200kVA Oil Type Motor Starting Auto Transformer 4.16kv1200kVA Oil Type Motor Starting Auto Transformer 4.16kv1200kVA Oil Type Motor Starting Auto Transformer 4.16kv1200kVA Oil Type Motor Starting Auto Transformer 4.16kv
1200kVA Oil Type Motor Starting Auto Transformer 4.16kv
Our Services
1. Pre sale service
a. make technical solution
b. send quotation, technical data sheet and drawing
c. prepare power transmission plan, testing plan,and shipment plan
2. In sale service
a. supervise the manufacturing schedule totally in accordance with the plan
b. send photos to customer during every manufacturing process(hold point)
c. inform the customer one week before testinng.
3. After sale service
a. installation and commissioning, training the workers
b. quick response within 12 hours any time
c. provide 12 months gurantee period normally.

 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now