Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Electric Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
No. | Name | Unit | Technical parameter | |
1. | Rated voltage | KV | 40.5 | |
2. | Rated current | A | 1250,1600,2000,2500 | |
3. | Rated short circuit breaking current | KA | 25 | 31.5 |
4. | Peak withstand current | 63 | 80 | |
5. | Short time current (4s) | 25 | 31.5 | |
6. | Rated short circuit making current | 63 | 80 | |
7. | Rated short circuit breaking times | Times | 30 | 30 |
8. | Operating sequence | O-0.3s-CO-180s-CO | ||
9. | Lightning impulse withstand voltage | KV | 185 | |
10. | Rated short time power frequency withstand voltage(1min) | 95 | ||
11. | Closing time | Ms | <=90 | |
12. | Opening time | <=70 | ||
13. | Energy stored time | S | <=15 | |
14. | Mechanical endurance | Times | 10000 | |
15. | Rated current breaking times | 10000 | ||
16. | Energy stored electric machine rated frequency | W | 275 | |
17. | Energy stored electric machine rated voltage | V | DC110 AC/DC220 | |
18. | Making electromagnet rated voltage | DC110 DC220 | ||
19. | Making electromagnet rated resistance | ¦¸ | 57.7 247 | |
20. | Making electromagnet rated current | A | DC1.91 DC0.89 | |
21. | Over current release current | 5 | ||
22. | Auxiliary switch rated current | AC10 DC5 | ||
23 | Contact moving distance | Mm | 25(+ or -)2 | |
24 | Contact travel | 8(+ or -)2 | ||
25 | Closing speed | M/s | 1.0 to 1.8 | |
26 | Opening speed | M/s | 1.0 to 1.8 | |
27 | Contact closing bouncing time | Ms | <=2 | |
28 | Phase to phase central distance | Mm | 350,400,460 | |
29 | Asynchronization of making contact | Ms | <=2 | |
30 | Each phase main circuit resistance | ¦Ì¦¸ | <=40 | |
31 | Wear thickness allowance of moving contact and static contact | Mm | <=3 |
1. |
Pre sale service |
a. |
make technical solution |
b. |
send quotation, technical data sheet and drawing |
c. |
prepare power transmission plan, testing plan,and shipment plan |
2. |
In sale service |
a. |
supervise the manufacturing schedule totally in accordance with the plan |
b. |
send photos to customer during every manufacturing process(hold point) |
c. |
inform the customer one week before testinng. |
3. |
After sale service |
a. |
installation and commissioning, training the workers |
b. |
quick response within 12 hours any time |
c. |
provide 12 months gurantee period normally. |
Thanks for choosing VILLE as your reliable partner and