Product introduction:
Load regulating power transformer is developed and produced according to the requirement of the market. It
can be widely used in urban & rural, industrial & agricultural power network, which has a great significance for
energy-saving and environment protection. The lamination method of this product's iron core is ladder form,
instead of the traditional iron core lamination technology, which improves the magnetic circuit distribution inside
the iron core. It can be seen as a revolution of transformer iron core manufacturing. Compared with the
traditional, the no-load loss, no-load current and noise of the new one decrease 20% respectively, and load
loss decreases 10%. The new product applies CAD, with advance design, reasonable structure, and excellent
materials. Each index complies with the standards of GB1094-1996 "Power Transformer" GB/T6451-1999
"Technical Parameters and Requirements of Three-phase Oil-immersed Type Power Transformer". Now its level
is the leading position of our country.
Range of application:
It can be widely used in urban power network as well as petrochemical, metallurgical, textile and humid,
inaccessible enterprises, and mining.
Features:
High reliability, advanced level of performance, economic indicators and reasonable;
Using phase-shaped core of three joints, curing paint brushing the surface to reduce wear and tear and noise;
Winding structure of a new oil road design is reasonable, with the new insulation to improve the mechanical
strength and the ability to engage in short-circuit;
Tank forms, beautiful, generous.
Technical parameters:
Three phase distribution transformers with natural cooling (ONAN) for outdoor use, hermetically sealed, without
conservator. |
TYPICAL DATA |
Rated power : 25 kVA |
Standard : IEC 60076 |
High Voltage : 480 V, ± 4 x 2,5% |
Low voltage : 237/137 V |
Vector group : Dyn 11 |
Approx. No Load losses : Max 90 W |
Approx. Load losses : Max 550 W |
Impedance : 4% |
Frequency : 60 Hz |
Cooling : ONAN |
Approx. dimensions :790 x 1100 x 500 mm |
Pole mounted version |
GENERAL DATA |
According to IEC-60076 |
- Max. ambient temperature: 50°C |
- Temp. rise oil/windings: 50°C/55°C |
BIL: 2 kV |
- Hermetically sealed, with nitrogen cushion |
- For outdoor installation |
- Corrugated sheet steel tank |
- Painting: 1x layer metal primer |
2x layer finishing paint; color RAL 7033 paint finish system suitable for tropical conditions |
- Cooling medium: oil Shell Diala B or equivalent |
- H.V. and L.V. windings copper |
CONNECTIONS |
- 3 pcs. H.V. through insulators DIN 42531 |
- 4 pcs. L.V. through insulator DIN 42530 |
- 2 pcs. Earthing connections M12 |
ACCESSORIES |
- Name and data plate |
9 position off circuit tap changer |
- Filling plug |
- Lifting-, pulling/ transport eyes |
- Overpressure (safety) valve |
- Horizontal LV terminal pad connectors |
Bracket for pole mounting |
* All above mentioned characteristics are at nominal current, 75°C winding temperature and frequency 60Hz. |
Work shop
Ville Electric Company will keep up with the century, the epoch,
Sincerely look forward to your cooperation and win-win!
Create brilliant!