Customization: | Available |
---|---|
Application: | Power, Electronic, Instrument, Rectifier |
Phase: | Three |
Still deciding? Get samples of US$ 50000/Piece
Order Sample
|
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
|
---|---|
Support payments in USD |
Secure payments: | Every payment you make at Made-in-china.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
A grounding transformer or earthing transformer is a type of auxiliary transformer used in three-phase electric power systems to provide a ground path to either an ungrounded wye or a delta-connected system.Grounding transformers are part of an earthing system of the network. They let three-phase (delta connected) systems accommodate phase-to-neutral loads by providing a return path for current to a neutral.
Grounding transformers are typically used to:
Grounding transformers most commonly incorporate a single winding transformer with a zigzag winding configuration, but may also be created with a wye-delta winding transformer.Neutral grounding transformers are very common on generators in power plants and wind farms.Neutral grounding transformers are sometimes applied on high-voltage (sub-transmission) systems, such as at 33 kV, where the circuit would otherwise not have a ground; for example, if a system is fed by a delta-connected transformer. The grounding point of the transformer may be connected through a resistor or arc suppression coil to limit the fault current on the system in the event of a line-to-ground fault.
33/0.4KV EARTHING TRANSFORMER | |||
Unit | Required | Offered | |
Manufacturer | |||
Type | Outdoor, oil immersed, self-cooled, hermetically sealed and core type | ||
Dielectric Type | Mineral Oil (NOT Askarel nor PCBs) |
||
Standards | IEC 60076/60354 | ||
Cooling system | ONAN | ||
Vector Group | ZNyn11 | ||
Protection class | IP55 | ||
Insulation class | A | ||
Size (Length x Width x Height) | mm | - | |
Rated Power | kVA | 200 | |
Efficiency at full load and 100% p.f | % | 98 | |
No load current | % | 5.5 | |
Rated Primary Voltage | kV | 33 | |
Rated Secondary Voltage | kV | 0.4 | |
Nominal Frequency | Hz | 50 | |
Number of phases | 3 | ||
Off-load tap changer | ±2 x 2.5% | ||
Number of taps | 5 | ||
Rated short circuit power | kA | 25 | |
Short circuit current (permanent) | kA | 0.078 | |
Permissible neutral current for 5sec | A | 4200 | |
Zero sequence Current : DB | A | 160 | |
Zero sequence Current : KB 5sec | A | 1050 | |
Zero sequence impedance | Ohm/phase | 10 | |
Test Voltages | |||
Power frequency withstand/Induced voltage test: -High voltage winding at 200Hz |
kV | 70 | |
Separate source voltage test: -High voltage winding at 60 sec -Low Voltage winding at 60 sec -Neutral winding at 60 sec |
kV kV kV |
70 |
|
Impulse withstand test voltage full wave 1.2/50micro sec. High voltage winding Low voltage winding Neutral winding |
kV kV kV |
170 - 95 |
|
Short-circuit impedance Voltage Ucc | % | 4% (±10%) | |
Non load losses P0 | W | ≤145 | |
Load Losses Pcc | W | ≤1750 | |
Noise level Lwa | dB | <50 | |
Maximum ambient temperature | oC C |
40 | |
Tank type | Sealed tank with bolted cover | ||
Maximum temperature rise oil/windings | oC |
≤50oC/55oC | |
Tests | Winding resistance, voltage ratio and phase displacement, no-load loss & current, load-loss and short circuit impedance, induced and separate source voltage withstand test. | ||
Color | RAL7033 | ||
Spare parts | Oil gauge with thermometer, repair paint, and silica gel for breather | ||
Guarantee | 1 year from the date of taking over certificate of the project. |
1. | Pre sale service |
a. | make technical solution |
b. | send quotation, technical data sheet and drawing |
c. | prepare power transmission plan, testing plan,and shipment plan |
2. | In sale service |
a. | supervise the manufacturing schedule totally in accordance with the plan |
b. | send photos to customer during every manufacturing process(hold point) |
c. | inform the customer one week before testinng. |
3. | After sale service |
a. | installation and commissioning, training the workers |
b. | quick response within 12 hours any time |
c. | provide 12 months gurantee period normally. |