• 132kv 11.5kv 25mva Mobile Substation
  • 132kv 11.5kv 25mva Mobile Substation
  • 132kv 11.5kv 25mva Mobile Substation
  • 132kv 11.5kv 25mva Mobile Substation

132kv 11.5kv 25mva Mobile Substation

Mobile: Substation
Transport Package: Nude Packing
Specification: IEC60076
Trademark: ville
Origin: China
Customization:
Gold Member Since 2007

Suppliers with verified business licenses

Rating: 5.0/5

Basic Info.

Model NO.
Czbt-25-132/11.5KV
HS Code
8504231100
Production Capacity
1000/Year

Product Description

Czbt1-132kv 132kv/11.5KV  movable Mobile power transofrmer substation

Outdoor,dust and water proof (132/11.5)kv,25mva Mobile substation according to IEC standard .
The Mobile substation consists of two trailer(A&B).

Trailer (A) Carries the following equipments:
* Three pcs lighting arrester of (120kv,10ka) .
*3-phase,two-pole,vertical break(145kv,630A,31.5KA/1SEC).disconnected switch with earth switch at transformer side.
*3-phase,vacuum circuit breaker(145kv,630a,31.5KA/1SEC).with spring operating mechanism.
*One,3-phase(132kv/11.5kv)25mva YND11 oil immersed power transformer with (17) steps on load tap changer(OLTC) at high voltage side with regulatio( ±10% of 132kv).
*One pcs lighting arrester of (75kv,10ka)at neutral point of 25mva power transformer.
*One,3-phase,75kva,11.5kv/380v-220v,znyn1,auxiliary&earthing transformer with neutral current 300A/10SEC.
*Safety fence.
*All current transformers for 132kv side and neutral point are bushing types.
Trailer (B) Carry the following equipments:
One cabinet dust and water proof contain the control panel,protection panel,A,C distribution board,metering and energy board and equipped with suitable air condition.
One cabinet contain the 12kv,air-insulation metal-enclosed switchgear the switchgear consists of (one panel for 12kv voltage transformer with surge arrester,one panel for 12kv incoming feeder,five panels for out going feeders).

One Cabinet contain 110V,D.C system( charger,battery and D.C distribution board) with suitable ventilation 
 
Technical requirements for electrical system:
132kv system 

*Highest system voltage 145kv 
*Impulse with stand voltage 
               For Bushing   650KV
               For winding   550KV 
               For Neutral 350KV 
*Power frequency withstand test voltage(for 1min) 
                For Bushing   275kv 
               For winding  230kv 
              For Neutral  140KV 
*Rated breaking capacity  31.5ka 
Creeage distance  ≥ 25mm/KV 
11.5KV System 
*Highest system voltage  12kv 
Impulse with stand voltage 
              For Bushing 75kv 
              for winding 75kv 
              for neutral  75kv 
*power frequency withstand test voltage(for 1 min).
              For bushing     28kv 
             for winding  28kv 
            for neutral     28kv 
*Rated breaking capacity    31.5KA
Creepage distance       ≥25mm/KV 
132kv 11.5kv 25mva Mobile Substation132kv 11.5kv 25mva Mobile Substation132kv 11.5kv 25mva Mobile Substation


132kv 11.5kv 25mva Mobile Substation

Technical feature:
1. Faster recovery of power 
>>The prefabricated mobile substation is applied to fully or partial replace the conventional substation and resume the power supply in case
     of emergency.
2.Flexible solution  
>>Help an area which suffers shortage of power supply capacity in heavy load season or period. Use as the temporary substation in areas
    with booming power demands that exceed the existing electric power capability,to ease the tension of power supply.
3. Temporary solution 
>>Work as a temporary substation in areas of permanent substation suspended due to the capital shortage or other kind of reason.
4. Reliable solution 
>>The prefabricated mobile substation is the flexible and reliable way for transportation with the complete equipment. It also saves
     investment in various aspects, concerning the land requisition, civil construction,equipment installation etc, which improves the reliability
     of power supply for the system.
5. Higher efficiency 
>>The prefabricated mobile substation provides with all the functions that a conventional substation has, as well as easy installation and
    quick into the service. It could be into operation at once on site after the connection of input and output cable only.
 
Our Advantage:
1.Various  special requirement from customer or typical specification .
2.Competitive price (Real Factory).
3.Excellent quality control and faster feedback .
4.Good service and after sales.
5.In time delivery.
6. Manufacturing after drawings approved.
7.OEM is acceptable.We can change the design as client's requirements.
 
Technical parameters
Main transformer capacity ( MVA): 5, 7.5, 10, 15, 20, 25, 31.5;
HV side Swith gear rated voltage ( KV ): 33, 66, 77, 110, 132, 138:
Rated current (A): 1250A, 2000A;
Rated short circuit break current (KA): 25, 31.5, 40;
LV side Switch gear rated voltage (KV): 6.6, 11, 13.8, 22, 33:
Rated current (A): 1250, 2000, 2500, 3150;
Rated short circuit break current (KA): 25, 31.5, 40

Our workshop
132kv 11.5kv 25mva Mobile Substation

Our international sales team
132kv 11.5kv 25mva Mobile Substation
Our Services

1.

Pre sale service

a.

make technical solution

b.

send quotation, technical data sheet and drawing

c.

prepare power transmission plan, testing plan,and shipment plan

2.

In sale service

a.

supervise the manufacturing schedule totally in accordance with the plan

b.

send photos to customer during every manufacturing process(hold point)

c.

inform the customer one week before testinng.

3.

After sale service

a.

installation and commissioning, training the workers

b.

quick response within 12 hours any time

c.

provide 12 months gurantee period normally.

Order Instructions
When you choose our company product, please offer following data:
Transformer model:                     
Rated capacity:                     kVA
Phase:Three-phase
           Single-phase
Frequency:50HZ
                  60HZ
Rated voltage ( H.V. / L.V. ):                
Tapping range: ±       ×       %
Insulation level: LI       AC       / LI       AC        kv
Veotor group:Dyn11
                      Yyno
                      Other
Short-circuit Impedance:        %
Cooling method:ONAN
                          ONAF
Tapping method:OLTC
                           OCTC
                          Other
Single line diagram for mobile substation 
Other requirement:                           
                 

Notes:
We also can design special products according to customer's particular requirements.
The final dimension is subject to outline drawing.

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

Gold Member Since 2007

Suppliers with verified business licenses

Rating: 5.0/5
Management System Certification
ISO 9001, ISO 9000, ISO 14001, ISO 14000, ISO 20000, IATF16949, ISO 14064, QC 080000, ANSI/ESD, ISO 29001, ISO 50001
Import & Export Mode
Have Own Export License
Terms of Payment
LC, T/T, D/P, PayPal, Western Union, Small-amount payment, Money Gram